| Part Number |
Conductor Construction | Cable | Weight Approx. |
Max. Conductor Resistance at 20°C |
Current Carrying Capacity |
Standard Length* |
||||
|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Cross- Section |
No. of Strands |
Diameter of Single wire max. |
Conductor Diameter Max. |
Insulation Wall Thickness Nom |
Overall Diameter Min/Max |
|||||
| D21819XX | 4.00 | 56 | 0.31 | 2.80 | 0.64 | 4.00/4.40 | 46 | 4.71 | 60 | 500 |
| D21823XX | 6.00 | 84 | 0.31 | 3.40 | 0.64 | 4.60/5.00 | 65 | 3.14 | 77 | 500 |
| D21827XX | 10.00 | 80 | 0.41 | 4.50 | 0.80 | 5.90/6.50 | 105 | 1.82 | 109 | 500 |
| D218A11XX | 12.00 | 96 | 0.41 | 5.40 | 0.80 | 6.60/7.40 | 120 | 1.52 | 120 | 500 |
| D21828XX | 16.00 | 126 | 0.41 | 6.30 | 0.80 | 7.70/8.30 | 163 | 1.16 | 147 | 500 |
| D21856XX | 20.00 | 152 | 0.41 | 6.90 | 0.88 | 8.10/9.10 | 215 | 0.955 | 170 | 500 |
| D21830XX | 25.00 | 196 | 0.41 | 7.80 | 1.04 | 9.40/10.40 | 280 | 0.743 | 193 | 500 |
| D21832XX | 35.00 | 276 | 0.41 | 9.00 | 1.04 | 9.60/11.90 | 343 | 0.527 | 236 | 500 |
| D21834XX | 50.00 | 396 | 0.41 | 10.50 | 1.20 | 11.50/13.50 | 491 | 0.368 | 291 | 500 |
| Note : XX* : Please add last two digits in the part number as per the colour code given hereunder replacing XX while ordering. | ||||||||||
| Red – 01 | Yellow – 02 | Blue – 03 | Black – 04 | Green – 05 | Yellow-Green – 06 | Grey – 07 | Brown – 08 | White – 09 | Orange – 10 | Violet – 11 |
| Chocolate – 12 | Tan – 13 | Charcoal – 14 | LT Blue – 15 | DK Grey – 16 | LT Green – 17 | DK Green-18 | DK Blue – 19 | Purple – 20 | Pink – 21 | |
Other length as per Customer order.
Current Carrying Capacity given is for the maximum conductor operating temperature of 125°C and ambient temperature of 40°C.