IS 7098 (Part 1) – 2 Core APC Solid Conductor Unarmoured Cable
- Transmission and distribution of Power Industrial units
- Commercial and residential places
- Indoor and outdoor uses
- Cable ducts, cable trays conduits direct burial and underground burial where mechanical damage risk for cables
- Conductor : Annealed Plain Solid Copper Conductor Complying with IS 8130
- Insulation : Electron Beam Cross Linked Polyethylene 120°C
- Inner Sheath : PVC
- Jacket : PVC-ST2 (Optional : FRLS, ZHLS)
- Operating Temperature : -15 °C to +120 °C
- Short Circuit Temperature : 280 °C
- Bending radius (min) : 12 x Cable dia
- Rated Voltage :1100 V
- Test Voltage : 3 kV for 5 mins
- Specification : IS 7098
- Electron Beam Cross Linked
- Enhanced Mechanical, Electrical, Thermal & Weathering properties
- Soldering iron resistant
- Resistance to corona effect
- Easy jointing & termination
- Better resistance to most chemicals, oils & acids
- Low direct electric losses
- High current carrying capacity
| Part Number |
Area (Nom.) |
Min. No.of Wires |
Insulation Thickness (Nom.) |
Sheath Thickness (Nom.) |
Approx.Overall Diameter |
Approx.Weight of Cable |
Max. Conductor Resistance at 20°C
|
Current Rating for EBXL-XLPE Cables(125°C) |
Current Rating for Chemically Cured XLPE Cables(90°C) |
Short Circuit Rating for 1sec |
| In Air |
In Duct |
In Ground |
In Air |
In Duct |
In Ground |
|
Sq.mm |
Nos. |
mm |
mm |
mm |
Kg/Km |
Ω/km |
Amps |
Amps |
KA |
| 239E1302 |
1.5 |
1 |
0.7 |
1.8 |
13.6 |
225 |
12.1 |
31 |
34 |
39 |
24 |
27 |
31 |
0.21 |
| 239E1602 |
2.5 |
1 |
0.7 |
1.8 |
14.4 |
264 |
7.41 |
43 |
43 |
50 |
33 |
34 |
40 |
0.36 |
| 239E1902 |
4 |
1 |
0.7 |
1.8 |
15.5 |
319 |
4.61 |
59 |
55 |
66 |
45 |
44 |
52 |
0.57 |
| 239E2302 |
6 |
1 |
0.7 |
1.8 |
16.6 |
385 |
3.08 |
74 |
68 |
84 |
57 |
54 |
67 |
0.86 |